Adjust GreenStar 2 Rate Controller™ Settings

  1. NOTE: This section describes ONLY initial settings for machines equipped with GreenStar 2 Rate Controllers. See GreenStar 2 Rate Controller Operator’s Manual for all other instruction regarding setting alarms, rates, additional calibration, or troubleshooting.

    PC9419
    PC9419-UN-12SEP06

    Setup Softkey

    PC12971
    PC12971-UN-27OCT10

    Press Setup softkey.



  2. Select implement type (E).

  3. Select LIQUID FERT. TOOL.

  4. Select or enter new implement name (F).

  5. Press Set-Up Sections (L).

  6. NOTE: See RATE CONTROLLER CHART—on next page.

    Enter number of sections and set section width.

  7. Disable fence row nozzles.

  8. Set switch box association as appropriate.

  9. Select Height Switch (Q) if equipped.

  10. Disable dual boom.

  11. N105242
    N105242-UN-08OCT13

    Select 3-WIRE section valve type (E).



  12. Select FAST control valve type (G).

  13. Enter correct tank size (H).

  14. Enter 2031 for control valve calibration (I).

  15. IMPORTANT: See calibration value (J) stamped on flowmeter tag.

    Enter flowmeter calibration value (J).

  16. Set flowmeter units to gal (K).

  17. Deselect flow return (M).

  18. Select pressure sensor (N).

  19. IMPORTANT: To calibrate pressure sensor (P), see Section 40 in GreenStar 2 Rate Controller manual using 20 mV/psi value.

    Calibrate pressure sensor (P).

  20. NOTE: Agitator valve operated manually.

    Deselect agitator valve (Q).


GreenStar 2 Rate Controller is a trademark of Deere & Company

KB78086,0000D53-19-20140818