| Symptom | Problem | Solution |
|
System Will Not Produce Sufficient Cooling
| Fan speed switch off |
Press setpoint adjust
switch on armrest console and adjust blower speed up or down with
selection dial.
|
| |
Compressor not functioning (both the large and small
air-conditioning hoses, exiting right-hand rear corner of cab, are
at the same temperature)
|
See your John Deere
dealer.
|
| |
High-pressure switch open. Insufficient air flow across
condenser
|
Clean condenser. Check
rotary wand duct for obstruction.
Clean air screen.
See your John Deere
dealer.
|
| |
Low-pressure switch open. Insufficient air flow across
evaporator
|
Clean cab filters. Check
cab fan operation.
See your John Deere
dealer.
|
| |
Low-pressure switch open. Low outside air temperature
|
Move temperature control
to warmer setting.
|
| |
Low-pressure switch open. Insufficient refrigerant level
(bubbles in sight glass)
|
See your John Deere
dealer.
|
| |
Heater valve partially on (with temperature knob set
for maximum cooling, feel both heater hoses exiting right-hand rear
corner of cab. If both are warm, valve is open)
|
See your John Deere
dealer.
|
| |
Insufficient blower speed
|
Increase blower speed.
|
| |
Debris on radiator screen
|
Clean screen.
|
| |
Compressor clutch not engaging
|
See your John Deere
dealer.
|
| |
Condenser is overheating
|
Clean screens, cores
and fins of condenser, oil cooler, and radiator.
|
| |
Burned out clutch field or faulty field
|
See your John Deere
dealer.
|
| |
Faulty high pressure or low pressure switches
|
Replace switches.
|
| |
Faulty A/C evaporator thermostat sensor
|
Replace A/C evaporator
thermostat sensor.
|
| |
Recirculating fan disconnected
|
Check connectors at
fan switch.
|
| |
Compressor partially or completely seized
|
Remove compressor for
service or replacement.
|
| |
Dirty filters
|
Clean filters.
|
| |
Broken or disconnected electrical wire
|
Check all terminals
for loose connections; check wiring for hidden breaks.
|
| |
Broken or disconnected cab ground wire
|
Check ground wire to
see if loose, broken, or disconnected.
|
| |
Expansion valve stuck in open position
|
Replace expansion valve.
|
| |
Expansion valve stuck shut
|
Replace expansion valve.
|
| |
Broken refrigerant line
|
Examine all lines for
evidence of breakage by external stress of rubbing wear.
|
| |
Leak in system
|
Evacuate system, apply
static charge, leak test system, and repair leak as necessary.
|
| |
Restriction in refrigerant system
|
Check for kinked hoses.
|
| |
Restriction in receiver/dryer
|
See your John Deere
dealer.
|
| |
Restriction in expansion valve
|
See your John Deere
dealer.
|
| |
Compressor shaft seal leaking
|
Replace the compressor
shaft seal.
|
| |
Excessive moisture in system, causing expansion valve
freeze up
|
Drain and recharge.
Replace receiver-dryer.
|
| |
Clogged cab roof inlet panel
|
Remove and clean.
|
| |
Evaporator fins clogged
|
Blow out evaporator
fins with compressed air.
|
| |
Too little refrigerant in system
|
Recharge system.
|
| |
Clogged screen in receiver-dryer
|
Discharge system; replace
receiver-dryer. Then evacuate and charge system.
|
| |
Excessive moisture in system
|
Discharge system; replace
receiver-dryer. Then evacuate and charge system.
|
| |
Air in system
|
Discharge, evacuate,
and charge system.
|