Spray Setup Page


Navigate to Spray Setup Page

BM011351
BM011351-UN-29MAR17

Menu Button → Sprayer Application Button → Setup Menu Softkey → Spray Setup Tab

  1. Select the Menu button.

  2. Select the Sprayer Application button.

  3. Select the Setup Menu softkey.

  4. Select the Spray Setup tab.


Spray Setup Page

BM017145
BM017145-UN-17NOV16

Spray Setup Page

A - Application Rates

B - Minimum Pressure

C - Spray Off Pressure

D - Tank Volume

E - Spray System MIN MAX

F - Boom Pressure Relief

G - Alarm Setup

H - Boom Charge

The following settings are displayed and can be changed:

  • Application Rates 1, 2, or 3 (A): Allows the operator to set three different target application rates. The preset application rates are displayed at the Sprayer Main Page when one of the application rates 1, 2, or 3 are selected at the rate select switch.
  • Minimum Pressure (B): Allows the operator to set a minimum pressure to be maintained while spraying.
  • Spray Off Pressure (C): Allows the operator to set the pressure to be maintained while not spraying. Typically used to maintain high-pressure setting for agitation when not spraying. It should not be used as a means for spray boom charge compensation.
  • Tank Volume (D): Allows the operator to set the solution tank volume.
  • Spray System MIN MAX (E): Allows the operator to adjust the response time of the SprayStar™ rate control.
  • Boom Charge (H): Allows the operator to charge the spray boom at an automatically calculated pressure (spray boom charge pressure) for 3 s after the master on-off switch is pressed ON.
  • Boom Pressure Relief (F): Allows the operator to activate the spray boom pressure relief feature.
  • Alarm Setup (G): Allows the operator to turn on or off a flow rate error, sections off and ladder alarms.


SprayStar is a trademark of Deere & Company

DV15698,00001AF-19-20170406