Set Minimum Pressure
Minimum Pressure Setting
Determine and set the minimum pressure required using the following
procedures:
-
Unfold the spray booms.
-
Turn on all the spray control switches for each spray boom section.
-
Navigate to Spray Setup tab (B).

BM011351-UN-29MAR17
Menu Button → Sprayer Application Button →
Setup Menu Softkey → Spray Setup Tab

BM002465-UN-30MAR17
Sprayer Setup Page

BM002466-UN-24SEP15
Popup Keypad

BM002467-UN-06JAN17
Sprayer Main Page
A - Sprayer Main Softkey
B - Spray Setup Tab
C - Minimum Spray Pressure Input Box
D - Popup Keypad
E - Accept Button
F - Spray Off Pressure Input Box
G - Manual Target Pressure Input Box
-
Select the minimum spray pressure input box (C).
-
Enter 0 using the popup keypad (D).
-
Select the Accept button (E) to accept
the new value.
-
Turn the rate control switch to the manual pressure setting
(MAN position).
-
Select the spray off pressure input box (F).
-
Enter 0 using the popup keypad (D).
-
Select the Accept button (E) to accept
the new value.
-
Turn on the solution pump and spray system master switch.
-
Select the Sprayer Main softkey (A).
-
Select the manual target pressure input box (G).
-
Add increments of 6.9 kPa (0.069 bar) (1 psi) until all nozzle
body check valves open and all nozzles are spraying at full pattern.
Note the pressure value when this occurs.
-
Select the minimum spray pressure input box (C).
-
Enter the noted pressure from previous step.
-
Select the Accept button (E) to accept
the new value.
Spraying at Low Pressures
When spraying at low application pressures, use check valves
with lower pressure settings for optimum performance. Using nozzle
bodies with higher pressure check valves than the lowest targeted
application pressure when driving slow can cause nozzles to shut off
and therefore cause erratic application rates.

BM011352-UN-30MAR17
The spray rate control unit (SRC) attains the minimum pressure
when the spray system master switch is on and in auto mode.
Pressure setting needs to be higher than the nozzle check valve
pressure to keep all the check valves open, but not too high to prevent
over-application during normal speed adjustments in the field. If
minimum pressure is set too close to operating pressure, erratic operation
and over-application can result.
NOTE: Viscosity of carrier may affect minimum pressure required.
Perform procedure for carrier being applied. Review this procedure
whenever changing nozzle sizes, types, or when nozzle check valves
have been replaced.
Standard Factory Equipment
The spray boom has 83 kPa (0.83 bar) (12 psi) check valves as
standard equipment. Other check valves available through SprayMaster parts
include 21 kPa (0.21 bar) (3 psi), 69 kPa (0.69 bar) (10 psi), and
172 kPa (1.72 bar) (25 psi) settings. These pressures determine at
what pressure nozzles shut off.
Diaphragms:
-
EPDM
-
Viton: Better resistance to more chemicals
|
SprayMaster is a trademark of Deere & Company
|
FC59002,000007C-19-20170406
|
|