-
Select System tab.
-

PC12277-UN-16SEP09
Control Valve Type

PC10645-UN-11OCT07
Dual Valve System
A - Control Valve Type Drop-Down Menu
Select Control Valve Type from drop-down (A).
NOTE: If 2-wire valve is required and not shown in the drop-down,
adjust number of implement sections in earlier Implement Setup (see
component compatibility section).
-

PC12985-UN-28OCT10
Control Valve Calibration
A - Control Valve Calibration
B - Tank Capacity
C - Tank Capacity Displayed
D - Tank Capacity Units
Select and enter Control Valve Calibration number (A).
NOTE: Table shows recommended values. Fine-tune control valve
calibration valve for optimal performance (see fine-tuning procedure
in Troubleshooting section).
-
Select and enter maximum Tank Capacity (B).
-
Select Tank Capacity Displayed from drop-down (C).
-
Select Tank Capacity Units from drop-down (D).
|
Standard Valve Type
|
Valve Calibration Number (XXYZ)
|
|
Raven 165
|
2513
|
|
Raven™ 894
|
2513
|
|
Raven™ 125
|
2513
|
|
TeeJet®
|
1003
|
|
HARDI®
|
7051
|
|
Fast-Close Valve Type
|
Valve Calibration Number (XXYZ)
|
|
Raven™ 177
|
0753
|
|
HINIKER Servo Valve (8160 Monitor Compatible)
|
0433
|
|
Fast-Close Valve Type
|
Valve Calibration Number (XXYZ)
|
|
Raven™ 177
|
0753
|
|
HINIKER™ Servo Valve (8160 Monitor Compatible)
|
0433
|
NOTE: These are recommended values. It is recommended to fine
tune control valve calibration number for optimal performance (see
fine tuning procedure in Troubleshooting section).
-

PC20626-UN-18DEC14
A - Flowmeter Calibration Input Box
B - Flowmeter Units Drop-down Menu
C - Pressure Sensor 1 Checkbox
D - Pressure Sensor 2 Checkbox
E - Calibrate Pressure Sensor Button
Select and enter Flowmeter Calibration (A) as stamped on
valve.
NOTE: Most flowmeters have an attached tag indicating the recommended
calibration number. Enter this number as the initial flowmeter calibration
value. It is not necessary to enter an additional product mass conversion
value as the controller does it automatically.
-
Select Flowmeter Units from drop-down (B).
-
Select Pressure Sensor 1 (C) if sensor is installed. If using
more than one pressure sensor, select Pressure Sensor 2 (D). If a
pressure sensor is selected, pressure indicator displays on Menu instead
of flow rate.
-
Select Calibrate Pressure Sensor button (E) and follow the onscreen
instructions. Once calibration is completed, select Setup softkey
to return to System Setup.
(Refer to Sprayers and Liquid Fertilizer Tool Diagnostics.)