Setup Wizard — NH3 Tool

PC8663
PC8663-UN-29APR15

Menu Button

PC22295
PC22295-UN-21MAR16

John Deere Rate Controller 2000 Button

PC22296
PC22296-UN-21MAR16

Setup Softkey


  1. Select Menu button.

  2. Select John Deere Rate Controller 2000 button.

  3. Select Setup softkey.

  4. PC22816
    PC22816-UN-30JUN16

    PC22298
    PC22298-UN-13APR16

    A - Implement Tab

    B - Change / New Button

    C - Edit Button

    D - Remove Button

    E - Setting Tab

    F - Alarms Tab

    G - Rates Tab

    H - Select Profile Drop-down Menu

    I - Accept Button

    Select Implement tab (A).



  5. Select Change / New button (B).

    NOTE: If a profile is already configured, selecting Edit button (C) starts setup wizard for that profile and all steps must be completed to close the wizard.

    A maximum of eight profiles can be saved. Selecting Remove button (D) deletes selected profile.

    To edit individual settings without going through the wizard, select Settings (E), Alarms (F), or Rates (G) tabs.

  6. Select New Profile from drop-down menu (H).

  7. Select Accept button (I).

  8. PC22300
    PC22300-UN-21MAR16

    A - Profile Name

    B - Machine Type Drop-down Menu

    C - Application Width

    D - Units of Measurement Drop-down Menu

    E - Next Page Button

    Enter Profile Name (A).



  9. Select Machine Type from drop-down menu (B).

  10. Enter Application Width (C).

  11. Select units of measurement from drop-down menu (D).

  12. Select Next Page button (E).

  13. NOTE: NH3 applications can be configured with up to three products. For ease of instruction, this setup wizard uses a single product. If multiple products are selected, follow the setup wizard prompts and set up section groups.

    (Reference Setup Section Groups for more information.)

    PC22351
    PC22351-UN-28MAR16

    A - Number of Products

    B - Next Page Button

    Enter the Number of Products (A).



  14. Select Next Page button (B).

  15. PC22352
    PC22352-UN-28MAR16

    A - Application Mode Drop-down Menu

    B - Next Page Button

    Select Application Mode from drop-down menu (A).

    • NH3 — Conventional anhydrous ammonia applications.
    • NH3 AccuFlow HP+ — Specific for Raven AccuFlow HP™ Plus with a boost pump that increases the cooler capacity. John Deere Rate Controller 2000 has the ability to control the PWM valve on the boost pump.



  16. Select Next Page button (B).

  17. PC22353
    PC22353-UN-28MAR16

    A - Number of Sections

    B - Equal Width Sections Checkbox

    C - Next Page Button

    Enter Number of Sections (A).



  18. If applicable, select Equal Width Sections checkbox (B).

  19. Select Next Page button (C).

  20. NOTE:

    PC22305
    PC22305-UN-21MAR16

    A - Section 1 Width

    B - Section 2 Width

    C - Section 3 Width

    D - Section 4 Width

    E - Next Page Button

    Total width of all sections must be equal to total application width. If Equal Width Sections was selected, application width is evenly divided by number of sections.

    Enter width for each section (A—D).



  21. Select Next Page button (E).

  22. NOTE:

    PC22306
    PC22306-UN-21MAR16

    A - Previous Page Button

    B - Next Page Button

    Graphic displays each section width and output driver that controls each section valve. Verify that implement wiring is correct. Application width and section widths may only be edited in the setup wizard. If needed, select Previous Page button (A) to make corrections.

    Review Setup Sections and select Next Page button (B).



  23. NOTE:

    PC22307
    PC22307-UN-21MAR16

    A - Pressure Sensor 1 Drop-down Menu

    B - Pressure Sensor 2 Drop-down Menu

    C - Next Page Button

    Raven AccuFlow HP™ Plus is automatically configured with two pressure sensors.

    Custom sensors do not function properly until a calibration is completed.

    If equipped, select pressure sensor configuration from drop-down menus (A and B).



  24. Select Next Page button (C).

  25. NOTE:

    PC22308
    PC22308-UN-21MAR16

    A - Pressure Sensor 1 Minimum

    B - Pressure Sensor 2 Minimum

    C - Pressure Sensor 1 Maximum

    D - Pressure Sensor 2 Maximum

    E - Pressure Sensor 1 Alarm Checkbox

    F - Pressure Sensor 2 Alarm Checkbox

    G - Next Page Button

    Pressure alarm settings are based on operator preference. Set up alarms so they notify operator before system needs attention.

    If sensors were specified, set up pressure alarms:

    1. Enter Minimum Pressure (A and B).

    2. Enter Maximum Pressure (C and D).

    3. To enable sensor minimum and maximum alarm, select Alarm checkbox (E and F).

    4. Select Next Page button (G).



  26. CAUTION: Selecting the wrong valve type may result in valves opening unexpectedly. To avoid injury from exposure to chemicals, verify the correct valve is selected. Review control valve type before moving John Deere Rate Controller 2000 between implements.

    PC22354
    PC22354-UN-28MAR16

    A - Control Valve Type Drop-down Menu

    B - Valve Response Rate

    C - Control Deadband

    D - Valve Delay

    E - Next Page Button

    NOTE: Controller utilizes control valve to manipulate application rates.

    AccuFlow HP™ Plus is automatically configured with a single fast close valve.

    Select Control Valve Type from drop-down menu (A).

    NOTE: Entry fields vary for each control type selected. Use default values for initial setup.

    (For more information, reference Adjust Control Valve.)



  27. Enter Valve Response Rate (B).

  28. Enter Control Deadband (C)

  29. Enter Valve Delay (D).

  30. Select Next Page button (E).

  31. NOTE:

    PC22355
    PC22355-UN-28MAR16

    A - Flowmeter Calibration

    B - Next Page Button

    Most flowmeters are marked with a calibration number and pulse/units to use for the initial setup. Verify units of measure marked on flowmeter. If needed, convert to pulses per 10 pounds of actual nitrogen. NH3 contains 4.22 lbs of actual nitrogen per gallon.

    pulses / 10 lbs = ((?) pulses / 10 gallons) / 4.22

    Additional flowmeter calibration is recommended.

    (For more information, reference Calibrate Flowmeter.)

    Enter Flowmeter Calibration (A).



  32. Select Next Page button (B).

  33. NOTE:

    PC22357
    PC22357-UN-28MAR16

    A - Tank Level

    B - Current Level

    C - Low Tank Level

    D - Low Tank Level Alarm Checkbox

    E - Next Page Button

    John Deere Rate Controller 2000 estimates tank level based on the calculated applied volume.

    Enter Tank Capacity (A).



  34. Enter Current Level (B).

  35. If desired, enter Low Tank Level (C) and select Low Tank Level Alarm checkbox (D).

  36. Select Next Page button (E).

  37. PC22358
    PC22358-UN-28MAR16

    A - Rate 1 Preset Value

    B - Rate 2 Preset Value

    C - Rate 3 Preset Value

    D - Bump Rate

    E - Rate Selection Drop-down Menu

    F - Rate Smoothing Checkbox

    G - Rate Smoothing Percentage

    H - Next Page Button

    Enter up to three Preset Rate Values (A—C). Rate 1 preset value is required.



  38. Enter Rate Bump (D).

  39. Select Rate Selection from drop-down menu (E) to choose rate type displayed on main run page.

    • Predefined — Displays selection buttons for Preset Rate Values.
    • Rate Bump — Displays plus (+) and minus (-) buttons that increment target rate by Rate Bump value.
    • Map Based — Displays prescription target rate for current GPS location.

      (Reference Apex™ or MyJohnDeere.com for more information about creating prescriptions.)


  40. NOTE: Rate smoothing removes small fluctuations in the as-applied rate values. The displayed as-applied rate remains constant until rate increases or decreases by more than the set rate smoothing percentage.

    Default is 3% and can be set between 3—15%.

    If desired, select Rate Smoothing checkbox (F) and enter Rate Smoothing Percentage (G).

  41. Select Next Page button (H).

  42. NOTE:

    PC22359
    PC22359-UN-28MAR16

    A - Off Rate Alarm

    B - Off Rate Alarm Checkbox

    C - Section Valve Status Feedback Alarm Checkbox

    D - Next Page Button

    If enabled, Off Rate Alarm displays if the system detects a rate change greater than the entered percentage for more than 5 seconds.

    If desired, enter Off Rate Alarm (A) and select Alarm checkbox (B).



  43. If desired, select Section Valve Status Feedback Alarm checkbox (C).

  44. Select Next Page button (D).

  45. PC22360
    PC22360-UN-28MAR16

    Review Setup Summary and select Accept button (A).




AccuFlow HP is a trademark of Raven Industries Inc.

Apex is a trademark of Deere & Company

RW00482,0000699-19-20160630