-

PC22295-UN-21MAR16
John Deere Rate Controller 2000 Button
Select the John Deere Rate Controller 2000 button.
-

PC22296-UN-21MAR16
Setup Softkey
Select the Setup softkey.
-

PC24937-UN-03NOV17
A - Implement Tab
B - Change / New Button
C - Edit Button
D - Remove Button
E - Settings Tab
F - Alarms Tab
G - Rates Tab
Select the Implement tab (A).
-
Select the Change / New button (B).
If a profile is already configured, selecting the Edit
button (C) starts the setup wizard for the selected profile and all
the steps must be completed to close the wizard.
A maximum
of eight profiles can be saved. Selecting the Remove button (D) deletes
the selected profile.
To edit individual settings without going through the wizard,
select Settings (E), Alarms (F), or Rates (G) tab. If settings are
grayed out, user must enter the wizard to edit the profile.
-

PC22298-UN-13APR16
H - Profile Drop-Down Menu
I - Accept Button
Select New Profile from the drop-down menu (H).
-
Select the Accept button (I).
-

PC24938-UN-03NOV17
A - Profile Name
B - Machine Type Drop-Down Menu
C - Application Width
D - Units of Measure Drop-Down Menu
E - Next Page Button
Enter the Profile Name (A). This is the name displayed on
the run page.
-
Select pull-behind sprayer, self-propelled sprayer, or liquid
fertilizer tool from the Machine Type drop-down menu (B).
For this example, liquid fertilizer tool is selected.
-
Enter the Application Width (C).
-
Select the units of measure from the drop-down menu (D).
-
Select the Next Page button (E).
-

PC22301-UN-21MAR16
A - Application Mode Drop-Down Menu
B - Next Page Button
Select the Application Mode from the drop-down menu (A).
-
Liquid—Conventional liquid applications.
-
Liquid Tiered Boom (Direct)—Tiered boom applications using a
two-way boom valve with the ability to divert flow to different booms
based on flow rate. John Deere Rate Controller 2000 sends signals
directly to the valve for control.
-
Liquid Tiered Boom (External)—Tiered boom applications using
a two-way boom valve with the ability to divert flow to different
booms based on flow rate. John Deere Rate Controller 2000 sends signals
to an external module that controls the valve.
-
Liquid Constant Flow—Single boom applications using three-way
boom valves that divert flow back to the tank when in the off position.
-
Liquid Slurry Dragline—Liquid application for products that
do not have a control valve and require a large application rate,
like liquid manure.
-
Liquid Slurry—Conventional liquid application for products that
require a large application rate, like liquid manure.
When the master switch is turned off with the liquid slurry
dragline application, the John Deere Rate Controller 2000 totals page
continues to count flow for total gallons applied, but stops counting
applied acres.
When using a GreenStar 3 2630 Display, totals reported
to John Deere Operations Center are displayed incorrectly because
the display does not continue to count gallons when the master switch
is off. When using a Generation 4 Display, the totals match the John
Deere Rate Controller 2000 totals.
-
Select the Next Page button (B).
-

PC22302-UN-21MAR16
A - Number of Sections
B - Section Valve Type Drop-Down Menu
C - Equal Width Sections Checkbox
D - Fence Rows Enable Checkbox
E - Next Page Button
Enter Number of Sections (A).
-
Three-wire valves are required for tiered boom applications.
Select Section Valve Type from the drop-down menu (B).
(Reference Section Valves in Component Overview and Compatibility
for information on 2- and 3-wire valves.)
-
If applicable, select the Equal Width Sections checkbox (C).
-
Fence Rows Enable checkbox (D) is only available with
self-propelled or pull-behind sprayer machine type.
Fence row nozzles do not function when connected to a
Hagie self-propelled sprayer.
If applicable, select the Fence Rows Enable checkbox.
-
Select the Next Page button (E).
-

PC22304-UN-21MAR16
A - Left Fence Row Section Driver Drop-Down Menu
B - Right Fence Row Section Driver Drop-Down Menu
C - Next Page Button
Default (section drivers 17 and 18) is the recommended section
driver setting. Driver number assigned refers to the signal wire for
each fence row valve. (To verify correct implement wiring,
reference Main Harness [47-Pin Connector] Table.)
If fence rows were enabled:
-
Select Left Fence Row Section Driver from the drop-down menu
(A).
-
Select Right Fence Row Section Driver from the drop-down menu
(B).
-
Select the Next Page button (C).
-

PC22305-UN-21MAR16
A - Section 1 Width
B - Section 2 Width
C - Section 3 Width
D - Section 4 Width
E - Next Page Button
Total width of all the sections must be equal to the total
application width. If Equal Width Sections was selected, the application
width is evenly divided by the number of sections.
Enter the width for each section (A—D).
-
Select the Next Page button (E).
-

PC22306-UN-21MAR16
A - Previous Page Button
B - Next Page Button
Graphic displays each section width and driver that controls
each section valve. Verify that implement wiring is correct. Application
width and section widths may only be edited in the setup wizard. If
needed, select the Previous Page button (A) to make corrections.
Review Setup Sections and select the Next Page button (B).
-

PC22307-UN-21MAR16
A - Pressure Sensor 1 Drop-Down Menu
B - Pressure Sensor 2 Drop-Down Menu
C - Next Page Button
If the pressure sensor is not included in the drop-down menus
(A and B), then select Custom or Custom Low Pressure. Custom sensors
do not function properly until a calibration is completed.The number of pressure transducers that can be used depends on the
configuration and wiring.
If equipped, select the pressure sensor configuration from the
drop-down menus.
-
Select the Next Page button (C).
-

PC22308-UN-21MAR16
A - Pressure Sensor 1 Minimum
B - Pressure Sensor 2 Minimum
C - Pressure Sensor 1 Maximum
D - Pressure Sensor 2 Maximum
E - Pressure Sensor 1 Alarm Checkbox
F - Pressure Sensor 2 Alarm Checkbox
G - Next Page Button
Pressure alarm settings are based on operator preference.
Set up the alarms so they notify the operator before the system needs
attention.
If sensors were specified, set up pressure alarms:
-
When the alarm is enabled and the minimum pressure threshold
has been met, the control unit overrides flow control and attempts
to maintain the minimum pressure setting. This may result in over-application.
Enter the Minimum Pressure (A and B).
-
When the alarm is enabled and the maximum pressure threshold
has been met, the control unit overrides flow control and attempts
to maintain the maximum pressure setting. This may result in under-application.
Enter the Maximum Pressure (C and D).
-
To enable sensor minimum and maximum alarms, select the Alarm
checkboxes (E and F).
-
Select the Next Page button (G).
-

PC22348-UN-24MAR16
A - Agitator Valve Installed Checkbox
B - Agitator Duty Cycle Drop-Down Menu
C - Flow Return Installed Checkbox
D - Height Switch Checkbox
E - Next Page Button
If equipped with an agitator valve:
-
Select the Agitator Valve Installed checkbox (A).
-
Agitation Duty Cycle is based on 10 min run time intervals.
For example, if 20% is selected, the agitator runs for 2 minutes and
is off for 8 minutes.
If tank volume is at or below 20%
of total tank volume, agitation reduces to half the set duty cycle.
Select Agitator Duty Cycle from the drop-down menu (B).
-
Flow Return Installed (C) is only available for liquid
applications and can only be selected in the setup wizard. If Flow
Return Installed is selected and the implement is properly equipped,
the control unit opens a return valve to allow product to return to
the tank when all sections are closed.
If equipped, select the Flow Return Installed checkbox.
-
The Height Switch checkbox (D) is only available when
the Liquid Fertilizer Tool machine type is selected.
If equipped, select the Height Switch checkbox.
-
Select the Next Page button (E).
-

PC22349-UN-24MAR16
A - Tier 1 Max Flow Rate
B - Tier 2 Max Flow Rate
C - Percent Tier Disable
D - Next Page Button
Tiered boom systems control a directional valve to divert
flow to the different booms based on a flow rate trigger. This allows
the system to achieve the correct droplet size during various application
speeds.
If a tiered boom was selected for an application mode:
-
Enter Tier 1 Max Flow Rate (A).
-
On a 2-tier system, both tiers enable once Tier 1 Max Flow Rate
is achieved.
-
On a 3-tier system, the first tier disables and the second tier
enables once Tier 1 Max Flow Rate is achieved.
-
Enter Tier 2 Max Flow Rate (B).
-
On a 2-tier system, Tier 2 Max Flow Rate should be set to zero.
-
On a 3-tier system, both tiers enable once Tier 2 Max Flow Rate
is achieved.
-
Enter the Percent Tier Disable (C).
Percent Tier Disable is the percentage of volume per minute
setting that causes system to disable higher tier.
-
Select Next Page button (D).
-

PC22311-UN-22MAR16
A - Control Valve Type Drop-Down Menu
B - Valve Response Rate
C - Control Deadband
D - Valve Delay
E - Valve Advance
F - Control Effort
G - Next Page Button
Selecting the wrong valve type may result in valves opening
unexpectedly. To avoid injury from exposure to chemicals, verify that
the correct valve is selected. Review the control valve type before
moving the John Deere Rate Controller 2000 between implements.
The John Deere Rate Controller 2000 uses the control valve
to manipulate application rates.
Select the Control Valve Type from the drop-down menu (A).
Entry fields vary for each control type selected. The
values that populate in the field are default values and should permit
basic control of the valve. They may need to be adjusted to improve
valve performance.
(For more information, reference Adjust
Control Valve in this section.)
-
Enter the Valve Response Rate (B).
-
Enter the Control Deadband (C).
-
Enter the Valve Delay (D).
-
Enter the Valve Advance (E).
-
Enter the Control Effort (F).
-
Select the Next Page button (G).
-

PC22362-UN-29MAR16
A - Coil Frequency
B - High Limit
C - Low Limit
D - PWM Startup
E - Next Page Button
If PWM or PWM Close was selected as the control type valve:
-
Enter Coil Frequency (A).
(Reference the control valve manufacturer Operator’s Manual
for coil frequency.)
-
High and low limits from the GreenStar Rate Controller are based
on a 1-255 scale. To use these values for the John Deere Rate Controller
2000, divide the high and low limits by 255. Enter this percentage
for the High (B) and Low Limits (C).
Enter the High Limit.
-
Enter the Low Limit.
-
Enter the PWM Startup (D) for the PWM close valve or PWM Standby
for the PWM valve.
-
Select Next Page button (E).
-

PC22312-UN-22MAR16
A - Flowmeter Calibration
B - Flowmeter Pulse/Units Drop-Down Menu
C - Next Page Button
Most flowmeters are marked with a calibration number and
pulse/units to use for the initial setup. Additional flowmeter calibration
is recommended.(For more information, reference Calibrate
Flowmeter in this section.)
Enter the Flowmeter Calibration (A).
-
Select the Flowmeter Pulse/Units from the drop-down menu (B).
-
Select the Next Page button (C).
-

PC22313-UN-22MAR16
A - Tank Capacity
B - Current Level
C - Low Tank Level
D - Low Tank Level Alarm Checkbox
E - Tank Fill Monitor Checkbox
F - Next Page Button
John Deere Rate Controller 2000 estimates tank level based
on the calculated applied volume.
Enter the Tank Capacity (A).
-
Enter the Current Level (B).
-
If desired, enter the Low Tank Level (C) and select the Low
Tank Level Alarm checkbox (D).
-
Tank Fill Monitor (E) is only available for liquid applications.
Only select the checkbox if the implement is equipped with a tank
inlet flowmeter. While refilling, Tank Fill Monitor calculates the
tank volume without having to enter the Current Level manually.
If equipped, select the Tank Fill Monitor checkbox.
-
Select the Next Page button (F).
-

PC22315-UN-23MAR16
A - Tank Fill Flowmeter Calibration
B - Tank Fill Flowmeter Pulse/Units Drop-Down Menu
C - Next Page Button
Most flowmeters are marked with a calibration number and
pulse/units to use for the initial setup. Additional flowmeter calibration
is recommended.(For more information, reference Calibrate
Flowmeter in this section.)
When filling with a flowmeter, the machine must be stationary.
If the Tank Fill Monitor was selected:
-
Enter the Tank Fill Flowmeter Calibration (A).
-
Select the Tank Fill Flowmeter Pulse/Units from the drop-down
menu (B).
-
Select the Next Page button (C).
-

PC24941-UN-27NOV17
A - Decimal Shift Drop-Down Menu
B - Rate 1 Preset Value
C - Rate 2 Preset Value
D - Rate 3 Preset Value
E - Rate Bump
F - Rate Selection Drop-Down Menu
G - Rate Smoothing Checkbox
H - Rate Smoothing Percentage
I - Standby Pressure Checkbox
J - Standby Pressure
K - Next Page Button
Decimal shift allows for higher resolution of target and
displayed application rates by including additional decimal places.
It applies to all products of the same type, such as liquid or granular.If the decimal is shifted one place, the maximum rate that can
be entered is decreased by a factor of 10. If the decimal is shifted
2 places, the maximum rate that can be entered is decreased by a factor
of 100. For example, 1000 is decreased to 100.0 with a decimal shift
of 1, and it is decreased to 10.00 with a decimal shift of 2.
Select the Decimal Shift from the drop-down menu (A).
-
Enter up to three Preset Rate Values (B—D). Rate 1 preset value
is required.
-
Enter the Rate Bump (E).
-
To choose the rate type displayed on main run page, select the
Rate Selection from the drop-down menu (F).
-
Rate smoothing removes small fluctuations in the as-applied
rate values. The displayed as-applied rate remains constant until
the rate increases or decreases by more than the set rate smoothing
percentage.
Default value is 3% and it can be set between
3—15%.
If desired, select the Rate Smoothing checkbox (G) and enter
the Rate Smoothing Percentage (H).
-
Standby Pressure is only available for PWM valve types.
PWM Startup is only available for PWM Close type valves.
If desired, select the Standby Pressure checkbox (I) and enter
the Standby Pressure (J). The control unit maintains this pressure
when all sections are turned off.
-
Select the Next Page button (K).
-

PC22363-UN-29MAR16
A - Off Rate Alarm
B - Off Rate Alarm Checkbox
C - Minimum Flow Rate
D - Next Page Button
If enabled, the Off Rate Alarm displays if the system detects
a rate change greater than the entered percentage for more than 5
seconds.
If desired, enter the Off Rate Alarm (A) and select the Alarm
checkbox (B).
-
Minimum Flow Rate (C) is the lowest flow rate the control
unit allows. If the application speed is too slow, minimum flow rate
applied may exceed the target rate.
If pressure sensor
1 minimum pressure alarm is enabled, the minimum flow rate is not
shown. The pressure sensor 1 minimum pressure is used to maintain
the spray pattern if the flow rate drops too low.
Enter the Minimum Flow Rate required to maintain the spray pattern.
(Reference chemical provider for recommended settings.)
-
Select the Next Page button (D).
-

PC22318-UN-23MAR16
Setup Summary
A - Accept Button
Setup Summary may appear differently based on the configuration
and options selected.
Review the Setup Summary and select the Accept button (A).