Daily (Prestarting) Service
-
Operate engine at rated speed and 50%—70% Load for a Minimum
of 30 Minutes. Perform every 2 weeks. (Generator Sets Only)
-
Check engine oil level.
-
Check coolant level.
-
Open fuel return shutoff valve (if equipped) and verify all
fuel return lines are free of restrictions.
-
Check sea water pump and strainer, if equipped.
-
Check accessory drive belts.
-
Drain water from fuel filters.
-
Inspect wiring harness and fuses.
-
Check aftercooler condensate drain, if equipped.
-
Check air cleaner dust unloader valve and air filter restriction
indicator, if equipped.
-
Check air intake system.
-
Visual walkaround inspection.
|
|
RG,RG34710,5621-19-20180110
|
|