Emergency Stationary Engine Rule

RG19597-UN-20OCT10
Emissions Label
Emissions Label
After Tier 4 standards take effect, engine manufacturers of
emergency stationary engines that do not meet the standards for non-emergency
engines must add to each such emergency engine a permanent label (such
as the emission label as shown) which states that the engine is limited
to stationary emergency use. On John Deere engines this is stated
in the EPA emission label on each engine.
Fuel Requirements
Beginning 01 Oct 10, owners and operators of stationary engines
that use diesel fuel must only use diesel fuel meeting the requirements
of 40 CFR 80.510 (b), which requires that diesel fuel have a maximum
sulfur content of 15 PPM and either a minimum cetane index of 40 or
a maximum aromatic content of 35 volume percent.
Operation, Maintenance and Testing
The operation of emergency engines is limited to emergency operations
and required maintenance and testing.
There is no time limit on the use of emergency stationary engines
in emergency situations.
Maintenance and testing is limited to 100 hours per year. The
EPA has also included a provision that allows anyone to petition the
Administrator for additional hours, beyond the allowed 100 hours per
year, if such additional hours should prove to be necessary for maintenance
and testing reasons. The EPA will not require a petition for additional
hours if the hours beyond 100 hours per year for maintenance and testing
purposes are mandated by regulation such as State or Local requirements.
|
|
KW40574,0000003-19-20160512
|
|