Generator Set (Standby) Applications
To assure that the engine will deliver efficient standby generator
operation when needed, start engine and run at rated speed (with 50%—70%
load) for 30 minutes every 2 weeks. DO NOT allow engine to run for
an extended period of time with no load.
Biodiesel fuel is not recommended for standby equipment that
can have minimal fuel consumption (such as standby generators, fire
protection, etc.). For standby applications, use only petroleum based
diesel fuel with John Deere approved fuel conditioners and additives.
For fuel conditioners and additives, check with the local John Deere
dealer.
Petroleum diesel fuel should not be stored in service tanks
longer than two years even when using fuel additives. See the fuel
distributor or John Deere dealer for more information.
|
|