| RCP - Corner Post Control Unit Diagnostic Trouble Codes |
| Control Unit |
SPN |
FMI |
Pri. |
Indicator Light |
Description |
Effect |
| RCP |
158 |
00 |
2 |
|
Battery Voltage High indicates that the system battery voltage input to the corner post control unit is above 16 volts. |
Control Unit shutdown, Control unit functions not available. |
| RCP |
158 |
01 |
2 |
|
Battery Voltage Low indicates that the system battery voltage input to the corner post control unit is below 10.5 volts. |
Control Unit shutdown, Control unit functions not available. |
| RCP |
628 |
12 |
2 |
|
Program Memory Failure indicates that the control unit boot block detects that the application software is not executing (generated by the boot block). |
Control unit functions not available. |
| RCP |
1500 |
11 |
2 |
|
Corner Post Matrix Switch indicates that there is a problem with the corner post matrix switch panel. A key may be stuck or another problem exists within the corner post matrix switch. |
One or probably several switches of the corner post don't work correctly. |
| RCP |
1552 |
03 |
|
Air temperature control |
Temperature Set Point Potentiometer High indicates that switch is in the on OR defog position AND the sensor voltage input is above 4.5 volts. |
Temperature setting not possible. |
| RCP |
1552 |
04 |
|
Air temperature control |
Temperature Set Point Potentiometer Low indicates that switch is in the on OR defog position AND the sensor voltage input is below 0.5 volts. |
Temperature setting not possible. |
| RCP |
1552 |
13 |
3 |
Air temperature control |
Temperature Set Point Potentiometer Not Calibrated indicates that switch is in the on OR defog position AND the EEPROM indicates that the calibration was not done OR the value is out of max. / min. value. |
Temperature setting not possible. |
| RCP |
1553 |
03 |
|
Air temperature control |
Blower Setting Potentiometer High indicates that switch is in the on OR defog position AND the sensor voltage input is above 4.5 volts. |
Blower setting not possible. |
| RCP |
1553 |
04 |
|
Air temperature control |
Blower Setting Potentiometer Low indicates that switch is in the on OR defog position AND the sensor voltage input is below 0.5 volts. |
Blower setting not possible. |
| RCP - Corner Post Control Unit Diagnostic Trouble Codes |
| Control Unit |
SPN |
FMI |
Pri. |
Indicator Light |
Description |
Effect |
| RCP |
1553 |
13 |
3 |
Air temperature control |
Blower Setting Potentiometer Not Calibrated indicates that switch is in the on OR defog position AND the EEPROM indicates that the calibration was not done OR the value is out of max. / min. value. |
Blower setting not possible. |
| RCP |
300400 |
09 |
2 |
|
Metal Detector Control Unit Not Communicating indicates that the corner post control unit has not received a message from the metal detector control unit in the last 5 seconds. |
Metal detector control functions not available, harvesting operations not possible. |
| RCP |
300401 |
09 |
2 |
|
Armrest Control Unit Not Communicating indicates that the corner post control unit has not received a message from the armrest control unit in the last 5 seconds. |
Corner post control unit functions not availble. |
| RCP |
300402 |
09 |
2 |
|
SPFH Main Control Unit Not Communicating indicates that the corner post control unit has not received a message from the SPFH main control unit in the last 5 seconds. |
SPFH main control unit functions not available, harvesting operations not possible. |
| RCP |
300403 |
09 |
2 |
|
Overhead Control Panel Control Unit Not Communicating indicates that the corner post control unit has not received a message from the overhead control panel control unit in the last 5 seconds. |
Overhead control panel control unit functions not available. |
| RCP |
300404 |
09 |
2 |
|
Rear Wheel Drive Control Unit Not Communicating indicates that the corner post control unit has not received a message from the rear wheel drive control unit in the last 5 seconds AND the rear wheel drive enable request is received from the SPFH control unit. |
Rear wheel drive disabled. |
| RCP |
300405 |
09 |
2 |
|
Row Guidance Control Unit Not Communicating indicates that the corner post control unit has not received a message from the row guidance control unit in the last 5 seconds AND the row guidance enable request is received from the overhead control panel control unit. |
Row guidance control unit disabled. |
| RCP |
300406 |
03 |
|
|
Backlight Dimmer Potentiometer High indicats that the lights are on AND the output of the potentiometer voltage is above 4.5 volts. |
Default backlight to on. |